How do you calculate ground cable size?
Let we calculate the required GI earth conductor size for 20kA Fault Current at 0.5 sec. Approximately 185Sqmm. Generally, GI is availed in the busbar structure hence Or You can take any combination of conductor size such as 50×3.5 Sqmm or 25x8Sqmm etc….Earthing conductor size calculation Formula:
Material | Material Constant (k) |
---|---|
Aluminium | 126 |
How do you calculate cable size from KW?
Ok, let’s dive into calculations…
- Consumed Load = Total Load · Demand Factor: Consumed Load in KW = 80 · 1 = 80 KW.
- Consumed Load in KVA = KW/P.F.: Consumed Load in KVA = 80/0.8 = 100 KVA.
- Full Load Current = (KVA · 1000) / (1.732 · Voltage): Full Load Current = (100 · 1000) / (1.732 · 415) = 139 Amp.
What size ground do you need for a 200 amp service?
Per Article 250 of the NEC , The minimum size for a grounding conductor for a circuit protected by a 200 amp breaker is #6 copper or #4 Aluminum. If you are in the US, chances are your jurisdiction uses the NEC (National Electric Code) as a guide.
How is grounding system calculated?
Number of earthing pipe required = Fault Current / Max. current dissipated by one earthing pipe. Number of earthing pipe required = 50000/838 = 59.66 Say 60 No’s. Total number of earthing pipe required = 60 No’s.
How do you calculate cable size on a KW motor?
Cable size calculation formula: Cable size = 1.5 x Full Load Current. Example: Let’s we calculate required cable sizing for 5.5kW/7.5HP motor which is operated at 415V, 0.86pf. From our cable size calculator, the full load current of the 5.5kW motor is 10A.
How do you calculate wire size and breaker?
The general rule of thumb is that circuit breaker size should be 125\% of the ampacity of cable and wire or the circuit which has to be protected by the CB….According to the ohm’s law,
- I = P / V.
- I = 2000W / 120V.
- I = 16.66 A.
How far can I run 12 2 wire?
You can run a 12 gauge wire up to 70 feet on a 15 amp circuit. That number drops to 50 feet if you run 12 gauge wire on a 20 amp circuit.
How do you calculate the number of earthing pits?
Introduction. Number of Earthing Electrode and Earthing Resistance depends on the resistivity of soil and time for fault current to pass through (1 sec or 3 sec). If we divide the area for earthing required by the area of one earth plate gives the number of earth pits required.
What are the requirements for electrical grounding conductors?
Section 250.119 requires these conductors to be bare, covered, or insulated. Covered or insulated equipment grounding conductors shall have a continuous outer finish that is either green or green with one or more yellow stripes. Grounding Electrode— A conducting object through which a
What size wire is needed for load over 100A?
Step 3 (B) – Load in Step 1 is over 100A or conductors are sized 1/0 AWG and Larger select conductor that can handle the load from 75°C Column. Continuing on Paul’s take above, consider this, the National Electrical Code requirements for cable sizing/conductor sizing and over-current protection have always been fairly confusing and complex.
How to design a grounding system for AC substation?
List all data that must be known in the starting of Grounding System Design Calculations for AC Substation , Facilitate the design process by using the auto excel mathematical functions in performing the calculations, Provide a professional design concept for any Grounding System of AC Substation as per Standard IEEE 80-2000,
What is the size of the feeder overcurrent device?
The feeder overcurrent device must be sized not less than 125\% of 184A, 184A x 125\% = 230A. According to 240.6 (A) we must select a minimum 250A overcurrent device. Step 2 – Select the conductor to comply with 215.2, which requires the feeder conductor to be sized no less than 125\% of the continuous load, 184A x 125\% = 230A.